CLCGN - SULFURIC ACID, BATTERY ELECTROLYTE-STANDBY(FLOODED)
- MSDS: CLCGN
- Manufacturer: C AND D TECHNOLOGIES INC
- Product Name: SULFURIC ACID, BATTERY ELECTROLYTE-STANDBY(FLOODED)
- National Stock Number: 6140-01-106-8936
Product Identification
Product ID:SULFURIC ACID, BATTERY ELECTROLYTE-STANDBY(FLOODED)
MSDS Date:07/21/2000
FSC:6140
NIIN:01-106-8936
Status Code:A
MSDS Number: CLCGN
Responsible Party
BLUE BELL, PA 19422-0858
US
Emergency Phone: 610-828-9309/800-255-3924,CHEM TEL
Info Phone: 215-619-2700
Preparer: J. LEBLANC
Cage: 1K126
Contractor
Telephone: 215-619-2700
Cage: 1K126
Ingredients
SULFURIC ACID
CAS: 7664-93-9
RTECS: WS5600000
OSHA PEL 1 MG/M3
ACGIH TLV: 1 MG/M3
EPA Report Quantity: 1000 LBS
DOT Report Quantity: 1000 LBS
WATER
CAS: 7732-18-5
RTECS: ZC0110000
Hazards
Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:NO IARC:NO
Health Hazards Acute and Chronic:ACUTE:TISSUE DESTRUCTION ON CONTACT.
MAY CAUSE 2ND AND 3RD DEGREE BURNS OR BLINDNESS WITH PROLONGED
CONTACT. INGESTION WILL CAUSE CORROSIVE BURNS ON CONTACT. MAY BE
FATAL IF SWALLOWED. CHRONIC: INHALA TION OF MISTS MAY CAUSE UPPER
RESPIRATORY IRRITATION .
Explanation of Carcinogenicity:IARC CLASSIFIED "STRONG INORGANIC ACID
MIST CONTAINING SULFURIC ACID" CATEGORY 1 CARCINOGEN, CARCINOGENIC
TO HUMANS." NTP DESIGNATS STRONG INORGANIC SULFURIC MIST A KNOWN
CARCINOGEN." THIS DOES NOT A PPLY TO LIQUID FORMS OF SULFURIC ACID
OR SULFURIC ACID SOLUTIONS CONTAINED WITHIN BATTERY. INORGANIC
MIST IS NOT GENERATED UNDER NORMAL USE OF THIS PRODUCT.
Effects of Overexposure:IRRITATION OR BURNING OF EXPOSED TISSUES.
Medical Cond Aggravated by Exposure:RESPIRATORY DISORDERS MAY BE
AGGRAVATED BY PROLONGED INHALATION OF MISTS.
First Aid
First Aid:SKIN/EYES: FLUSH WITH WATER FOR 15 MINUTES. REMOVE
CONTAMINATED CLOTHING. IF IRRITATION CONTINUES, SEEK MEDICAL
ATTENTION. INGESTION: DO NOT INDUCE VOMITING. DRINK LARGE
QUANTITIES OF MILK OR WATER. G IVE CPR IF BREATHING HAS STOPPED.
SEEK MEDICAL ATTENTION IMMEDIATELY.
Fire Fighting
Extinguishing Media:DRY CHEMICAL, HALON, OR CARBON DIOXIDE.
Fire Fighting Procedures:VENTILATE THE AREA WELL. SCBA AND ACID
PROTECTIVE CLOTHING ARE RECOMMENDED.
Unusual Fire/Explosion Hazard:HYDROGEN GAS MAY BE PRESENT. HYDROGEN GAS
AND ACID MIST IS GENERATED UPON OVERCHARGE OR IN FIRE. VENTILATE
AREA.
Accidental Release
Spill Release Procedures:NEUTRALIZE SPILLED ELECTROLYTE WITH SODA ASH
OR SODIUM BICARBONATE UNTIL FIZZING STOPS. WHEN REACTION STOPS PH
SHOULD BE NEUTRAL AT 6-8. COLLECT RESIDUE AND PLACE IN A SUITABLE
CONTAINER. RESIDUE MAY BE HAZARDOUS WASTE. WHEN NEUTRALIZED, THE
SPILL IS NON-HAZARDOUS. PROVIDE ADEQUATE VENTILATION, HYDROGEN GAS
MAY BE GIVEN OFF DURING NEUTRALIZATION. CONTAIN LARGE SPILLS WITH
EARTH OR CLAY DIKES.
Neutralizing Agent:NEUTRALIZE ANY SPILLED ELECTROLYTE WITH SODA ASH OR
SODIUM BICARBONATE UNTIL FIZZING STOPS.
Handling
Handling and Storage Precautions:ADD WATER TO ACID AFTER NEUTRALIZATION
TO AVOID EXCESSIVE HEAT GENERATION. STORE IN COOL, DRY AREA AWAY
FROM REACTIVES AND COMBUSTIBLES. DO NOT STORE IN SEALED,
UNVENTILATED AREAS. PROVIDE SECONDARY C ONTAINMENT IF LARGE VOLUMES
ARE STORED.
Exposure Controls
Respiratory Protection:NIOSH APPROVED ACID MIST RESPIRATOR, IF OSHA PEL
IS EXCEEDED OR RESPIRATORY IRRITATION OCCURS.
Ventilation:GENERAL ROOM VENTILATION IS SUFFICIENT DURING NORMAL USE
AND HANDLING. RECOMMEND 2 TO 3 ROOM AIR CHANGES PER HOUR TO PREVENT
BUILDUP OF HYDROGEN GAS.
Protective Gloves:PROTECTIVE GLOVES; RUBBER OR NEOPRENE.
Eye Protection:CHEMICAL GOGGLES OR SAFETY GLASSES WITH SIDESHIELDS AND
A FULL FACE SHIELD.
Other Protective Equipment:ACID RESISTANT APRON OR CLOTHES.
Work Hygienic Practices:MAINTAIN EYEWASH AND DRENCH SHOWER IN AREA.
Supplemental Safety and Health
CONTRACTORS PART NUMBER: 8 CJCS-11EE. THIS ENTRY DESCRIBES THE SULFURIC
ACID ELECTROLYTE THAT IS PACKED SEPARATE AND SHIPPED SIMULTANEOUSLY
TOGETHER WITH BATTERY, STORAGE, LEAD-CALCIUM, DRY CHARGED. S EE
MSDS SERIAL NUMBER CLCGS FOR MSDS COVERING THE DRY CHARGED BATTERY.
Chemical Properties
HCC:C1
Boiling Pt:=112.8C, 235.F
Vapor Pres:145.8/MM HG
Vapor Density:>1
Spec Gravity:1.400 +/- .010
Evaporation Rate & Reference:<1(H2O=1)
Solubility in Water:100%
Appearance and Odor:CLEAR, COLORLESS LIQUID/ACRID SMELL
Stability
Stability Indicator/Materials to Avoid:YES
METALS AND COMBUSTIBLES CAN REACT WITH OXIDIZING OR REDUCING AGENTS..
Stability Condition to Avoid:THIS IS A STABLE MATERIAL.
Hazardous Decomposition Products:HYDROGEN GAS, SULFUR TRIOXIDE MAY BE
GENERATED DURING BATTERY OVERCHARGE CONDITIONS, IN FIRE AND AT HIGH
TEMPERATURES. IN FIRE MAY EMIT CO, CO2 AND SULFIDES.
Conditions to Avoid Polymerization:WILL NOT OCCUR.
Disposal
Waste Disposal Methods:BATTERY ELECTROLYTE IS A HAZARDOUS WASTE BY
CHARACTERISTIC OF CORROSIVITY. FOLLOW PROPER DISPOSAL AS ALLOWED BY
LOCAL ORDINANCES AND SITE PERMITS. ACID CONTAINED IN SCRAP
BATTERIES WILL BE RECYCLED AN D REUSED IF BATTERY IS HANDLED
THROUGH C&D LEAD-RECYCLING PROGRAM. RCRA WASTE DISPOSAL NO.:
D002-COR ROSIVE. CONTACT C&D FOR MORE INFORMATION.
Toxicology
Toxicological Information:CARCINOGENICITY: IARC HAS CLASSIFIED "STRONG
INORGANIC ACID MIST CONTAINING SULFURIC ACID" AS A CATEGORY 1
CARCINOGEN, A SUBSTANCE THAT IS CARCINOGENIC TO HUMANS. "NTP HAS
DESIGNATED STRONG INORGANIC SULFURIC MIST AS A KNOWN HUMAN
CARCINOGEN". THIS CLASSIFICATION DOES NOT APPLY TO LIQUID FORMS OF
SULFURIC ACID OR SULFURIC ACID SOLUTIONS CONTAINED WITHIN A
BATTERY. INORGANIC ACID MIST (SULFURIC ACI D MIST) IS NOT GENERATED
UNDER NORMAL USE OF THIS PRODUCT. MISUSE OF THE PRODUCT, SUCH AS
OVERCHARGING, MAY HOWEVER RESULT IN THE GENERATION OF SULFURIC ACID
MIST AT HIGHER LEVELS.
Ecology
Ecological:SULFURIC ACID CAN POSE A THREAT IF RELEASED TO THE
ENVIRONMENT.
Transport
Transport Information:FOR DOMESTIC, CANADIAN, AND EXPORT SHIPMENTS:
PROPER SHIPPING NAME: BATTERY FLUID, ACID; UN 2796; HAZARD CLASS:
8; PACKING GROUP: I I; LABEL: CORROSIVE; EMERGENCY RESPONSE
GUIDE:157 . BATTERY FLUID, ACID. HAZARD CLASS 8. PACKING GROUP
II. EMERGENCY RESPONSE GUIDE: 157. FOCAL POINT D TIR, PID:
BATTERY, STORAGE, LEAD-CALCIUM, DRY CHARGED, WITH CONTAINER OF
SULFURIC ACID ELECTROLYTE PACKED SEPARA TE AND SHIPPED
SIMULTANEOUSLY TOGETHER. P / N 8 CJCS-11EE. D.0.T. CLASS:
CORROSIVE.
Regulatory
Federal Regulatory Information:SEE 29 CFR 1910.268(B)(2). RCRA WASTE
DISPOSAL NO. D002. HMIS RATINGS: HEALTH: 2 (MODERATE);
FLAMMABILITY: 0 (INSIGNIFICANT); REACTIVITY: 1 (SLIGHT); OTHER: 0
(SLIGHT). NFPA RATING: HEALTH: 2 (MODERA TE); FLAMMABILITY: 0
(SLIGHT); REACTIVITY: 1 (SLIGHT); OTHER: CORR.
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.